VENT NK - centrifugal in-line fans ≤3890 m³/h

  • Attention! We recommend the higher quality and class centrifugal in-line fans AXC
  • VENT NK - in-line duct centrifugal fans, manufactured from high grade corrosion resistant pressed galvanised steel and supplied as standard with a prewired wiring junction box and a robust mounting foot
  • all model include an enclosed type, single-phase external rotor motor with factory matched backward curved nonstalling impeller, models 355 and 400 are manufactured in sheet steel protected against corrosion by cataforesis primer and black polyester paint finish
  • all models with ball bearings and safety thermal overload protection, 100N - 250N motors are IP44, class B insulation, 315N motor is IP44, class F insulation, 355N and 400N motors are IP54, class F
  • Impellers from 100 to 250 models are manufactured from injection moulded plastic
  • transported air temperature -20 - +70 °C (see technical specification)
  • made in Spain
  • 2 years warranty
  • Attention! If you want to install the fan on the cooker hood, you must install special filters before the fan to fully clean the contaminated air. These fans are designed to transport clean air. If the fan is installed without filters, the fan is not covered by the warranty.
  • it is recomended to install fan with anti-vibration sealing clamps:

 


Brand: Soler & Palau
Code
A
B
C
D D2 E* F* G* H* J*
VENT100NK 195 23 243 98            
VENT125NK 197 27 243 123            
VENT150NK 213 22 333 147            
VENT160NK 220 27 333 157            
VENT200NK 223 25 333 198            
VENT250NK 205 27 333 248            
VENT315NK 232 25 401 312            
VENT355N 410 25 508 354 314 552 100 170 587 10.5
VENT400N 431 25 568 399 354 628 100 185 647 10.5

 

Code
Voltage, V
Frequency, Hz
Capacity, m³/h
Power, W Current, A Noise level, dB(A)1.5m Speed, min-1 Working temperature, °C Weight, kg
VENT100NK 230 50/60 290 61 0.3 44 2600 -20 +60 3
VENT125NK 230 50/60 390 60 0.3 42 2620 -20 +60 3
VENT150NK 230 50/60 750 95 0.4 42 2550 -20 +60 5
VENT160NK 230 50/60 760 96 0.4 42 2560 -20 +60 5
VENT200NK 230 50/60 970 147 0.6 43 2720 -20 +60 5
VENT250NK 230 50/60 1030 149 0.6 50 2720 -20 +60 6
VENT315NK 230 50/60 1370 257 1.1 48 2790 -20 +60 8
VENT355N 230 50/60 2690 287 1.2 40 1404 -20 +70 18.8
VENT400N 230 50/60 3890 536 2.3 49 1380 -20 +50 22.2
VENT355NT 230/400 50 2640 270 1.1/0.6 43 1370 -20 +70 17
VENT400NT 230/400 50 3830 492 1.9/1.1 47 1370 -20 +50 22

 

Speed controllers (Attention! If you choose an electronic speed controller, the fan may emit an extraneous sound, the speed change will not be consistent, so we strongly recommend choosing a transformer speed controller):

VENT100-160NK VENT100-160NK VENT200NK-355N
EMTY05 - 0.5 A (fan may make noise) 5 step, transformer RVS - 0.5 A EETY15/EETX15 - 1.5 A (fan may make noise)
VENT100-250NK VENT 315 NK - 355 N VENT 400 N
5 step, transformer ESTR-1-10L10 - 1.0 A 5 step, transformer ESTR-1-15L22 - 1.5 A 5 step, transformer ESTR-1-35L22 - 3.5 A

 

Pressure loss diagrams