Fans for electrical cabinets RCQ 370.25 250x250 mm, 300 m³/h

  • RCQ 370.25 - axial fans supplied with grille and filter
  • usual type - the fan is installed at the bottom of the cabinet, filtering and emitting air, while through the top of the grille, hot air is expelled, creating a through exchange of air, obtaining efficient heat dissipation
  • E type - air extraction fan must be installed up and grille in the bottom - the opposite than standard version
  • UL type - approved by UL Institute in accordance with American Standard
  • low external profile
  • IP54 protection degree (IP44 on request)
  • maximum operating temperature - 70 °C
  • quick and functional assembly of the fan on the electrical cabinet through elastic click hooks and gasket pre-installed on the product
  • possible installation with screws (not provided)
  • body made of ABS self-extinguishing material grey RAL7035
  • ball bearing motor
  • grille in grey RAL7035 (RAL7032, black RAL9005 available on request)
  • easily removable grille to allow quick replacement of the filter
  • slotted external grilles to allow drainage of condensation
  • in accordance with European Standard EN 60529, EN 60335-2-80
  • made in Italy
  • 2 years warranty

Brand: ESEM
Code
A
B
C
D
E
RCQ 370.25 250 250 5.5 118 152x172

 

 

Drilling scheme for fan and grille assembly

Code
A
B
Ø C
RCQ 370.25 223 x 223 230÷234 x 230÷234 4.5

 

 

Code
Voltage, V
Frequency, Hz
Capacity, m3/h
Power, W Current, A Noise level, dB(A)3m Weight, kg
with filter without filter
RCQ 370.25, RCQ 370.25 E and RCQ 370.25 UL, RCQ 370.25 E-UL (UL only IP54 110-120V ac and IP54 220-240V ac)
IP54 12V dc 12 - 220 260 9 0.86 50 1.5
IP54 24V dc 24 - 220 260 9 0.43 50 1.5
IP54 48V dc 48 - 220 260 13 0.28 50 1.5
IP54 110-120V ac 110-120 50/60 260 300 25 0.22 50 1.6
IP54 220-240V ac 220-240 50/60 260 300 25 0.11 50 1.6

 

Pressure loss diagram

--> --> --> --> function tabs(selector) { console.log('aaa'); selector.each(function() { var obj = $(this); $(obj.attr('href')).hide(); obj.click(function() { $(selector).removeClass('selected'); $(this).addClass('selected'); $($(this).attr('href')).fadeIn(); $(selector).not(this).each(function(i, element) { $($(element).attr('href')).hide(); }); return false; }); }); $(selector).show(); $(selector).first().click(); }; tabs($('#tabs a')); -->
-->